GE b30 Instruction Manual page 224

Bus differential system
Hide thumbs Also See for b30:
Table of Contents

Advertisement

PRODUCT SETUP
Each enabled RxGOOSE monitors for interruption of the GOOSE messages it subscribes to based on the value in the
timeAllowedtoLive field of the last message received. If a new message is not received within that time interval, the
RxGOOSE assumes that connectivity is lost. FlexLogic operands (for example RxGOOSE1 On, RxGOOSE1 Off) reflect the
status of each RxGOOSE connectivity. An RxGOOSE connection is also considered lost after the UR finishes restart until a
message is received. While any RxGOOSE connectivity is lost, a common RxGOOSE Fail self-test is activated.
Messages that contain the value true in the ndsCom field are never accepted. Messages that contain the value true in the
simulation field (test field in edition 1.0 messages) are accepted only when the UR Test Mode Function setting is set to
Forcible or Isolated.
RxGOOSE messages can be received through any UR Ethernet port.
Navigate to Settings > Product Setup > Communications > IEC 61850 > GOOSE > RxGOOSE > RxGOOSE Messages >
RxGOOSE1 to access the settings that specify the messages to be accepted by the first RxGOOSE element. The settings
and functionality for the other RxGOOSE are similar. The following settings are available. They allow RxGOOSE1 to
recognize the GOOSE messages it is to accept. Most of these settings are automatically configured by UR Setup software
when an association to an RxGOOSE Boolean Input, RxGOOSE DPS Input, and/or RxGOOSE Analog Input is made as
described in the sections following this. Only settings R-RxGOOSE1 RECEPTION MODE, R-RxGOOSE1 SECURITY, and R-
RxGOOSE SRC IP need to be manually completed as the information is not contained in publisher SCL.
5
RxGOOSE1 MODE
Range: GOOSE, R-GOOSE
Default: GOOSE
When set to GOOSE, TxGOOSE1 messages are published in IEC 61850 8 1:2011 GOOSE format. When set to R-GOOSE,
TxGOOSE1 messages are published in Routable GOOSE format according to IEC 61850 90-5. When set to R-GOOSE, the
R-RxGOOSE DST IP needs to be a valid multicast or unicast IP address.
RxGOOSE1 goID
Range: 0 to 129 Visible String characters
Default: empty string
If the entered value has one or more characters, the goID field of incoming GOOSE messages must exactly match this
value for the message to be accepted as a valid RxGOOSE1 message. If the entered value is the empty string, RxGOOSE1
does not check the value received in the goID field.
If the publisher is a UR 7.3x series device, this setting needs match the value of the publisher's TxGOOSE GoID setting.
5-58
Figure 5-20: IEC 61850 RxGOOSE Messages panel
CHAPTER 5: SETTINGS