Rxgoose Status; Rxgoose Statistics; Digital Counters - GE b30 Instruction Manual

Bus differential system
Hide thumbs Also See for b30:
Table of Contents

Advertisement

STATUS

6.3.8 RxGOOSE status

ACTUAL VALUES  STATUS  RxGOOSE STATUS
 RxGOOSE
 STATUS
The B30 is provided with optional IEC 61850 capability. This feature is specified as a software option at the time
of ordering. See the Order Codes section of chapter 2 for details.
The
All RxGOOSE Online
Input.

6.3.9 RxGOOSE statistics

ACTUAL VALUES  STATUS  RxGOOSE STATISTICS  RxGOOSE 1(64)
 RxGOOSE 1
The B30 is provided with optional IEC 61850 capability. This feature is specified as a software option at the time
of ordering. See the Order Codes section of chapter 2 for details.
6
— State number. The most recently received value in GOOSE message field stNum. The publisher increments stNum
stNum
each time that the state of one or more of the GOOSE message members is sent with a revised value.
— Sequence number. The most recently received value in GOOSE message field sqNum. The publisher sets sqNum
sqNum
to zero each time the state of one or more of the GOOSE message members is sent with a new value, and it increments it
whenever a GOOSE message is resent without any member value change.

6.3.10 Digital counters

ACTUAL VALUES  STATUS  DIGITAL COUNTERS  DIGITAL COUNTERS Counter 1(8)
 DIGITAL COUNTERS
 Counter 1
The present status of the eight digital counters displays here. The status of each counter, with the user-defined counter
name, includes the accumulated and frozen counts (the count units label also appears). Also included, is the date and time
stamp for the frozen count. The
6-6
All RxGOOSE Online:
Yes
RxGOOSE 1 Status:
Offline
RxGOOSE 64 Status:
Offline
actual value does not consider RxGOOSE that are not configured or are not used by any RxGOOSE
RxGOOSE 1
stNum:
RxGOOSE 1
sqNum:
Counter 1
0
Counter 1 FROZEN:
0
Counter 1 FROZEN:
1970/01/01 00:00:00
Counter 1 MICROS:
0
value refers to the microsecond portion of the time stamp.
COUNTER 1 MICROS
Range: Yes, No
Range: Online, Offline
Range: Online, Offline
Range: 0 up to 4,294,967,295
0
Range: 0 up to 4,294,967,295
0
ACCUM:
Range: YYYY/MM/DD HH:MM:SS
Range: 0 to 4294967295 in steps of 1
B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL
CHAPTER 6: ACTUAL VALUES

Advertisement

Table of Contents
loading

Table of Contents