Disconnect Switches - GE b30 Instruction Manual

Bus differential system
Hide thumbs Also See for b30:
Table of Contents

Advertisement

CHAPTER 5: SETTINGS

5.5.5 Disconnect switches

SETTINGS  SYSTEM SETUP  SWITCHES  SWITCH 1(24)
 SWITCH 1
The disconnect switch element contains the auxiliary logic for status and serves as the interface for opening and closing of
disconnect switches from SCADA or through the front panel interface. The disconnect switch element can be used to
create interlocking functionality. For greater security in determination of the switch pole position, both the 89/a and 89/b
auxiliary contacts are used with reporting of the discrepancy between them. The number of available disconnect switches
is four per breaker.
— This setting enables and disables operation of the disconnect switch element.
SWITCH 1 FUNCTION
— Assign a user-defined name (up to six characters) to the disconnect switch. This name is used in flash
SWITCH 1 NAME
messages related to disconnect switch 1.
— This setting selects "3-Pole" mode, where disconnect switch poles have a single common auxiliary
SWITCH 1 MODE
switch, or "1-Pole" mode where each disconnect switch pole has its own auxiliary switch.
— This setting selects an operand that creates a programmable signal to operate a contact output to open
SWITCH 1 OPEN
disconnect switch 1.
— This setting selects an operand that prevents opening of the disconnect switch. This setting can be
SWITCH 1 BLK OPEN
used for select-before-operate functionality or to block operation from a panel switch or from SCADA.
B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL
SWITCH 1
FUNCTION: Disabled
SWITCH 1 NAME:
SW 1
SWITCH 1 MODE:
3-Pole
SWITCH 1 OPEN:
Off
SWITCH 1 BLK OPEN:
Off
SWITCH 1 CLOSE:
Off
SWITCH 1 BLK CLOSE:
Off
SWTCH 1 ΦA/3P CLSD:
Off
SWTCH 1 ΦA/3P OPND:
Off
SWITCH 1 ΦB CLOSED:
Off
SWITCH 1 ΦB OPENED:
Off
SWITCH 1 ΦC CLOSED:
Off
SWITCH 1 ΦC OPENED:
Off
SWITCH 1 TOPERATE:
70 ms
SWITCH 1 ALARM
DELAY:
0.000 s
SWITCH 1 EVENTS:
Disabled
Range: Disabled, Enabled
Range: up to six alphanumeric characters
Range: 3-Pole, 1-Pole
Range: FlexLogic operand
Range: FlexLogic operand
Range: FlexLogic operand
Range: FlexLogic operand
Range: FlexLogic operand
Range: FlexLogic operand
Range: FlexLogic operand
Range: FlexLogic operand
Range: FlexLogic operand
Range: FlexLogic operand
Range: 0 to 65535 ms in steps of 1
Range: 0.000 to 65.535 s in steps of 0.001
Range: Disabled, Enabled
SYSTEM SETUP
5
5-135

Advertisement

Table of Contents
loading

Table of Contents