GE b30 Instruction Manual page 466

Bus differential system
Hide thumbs Also See for b30:
Table of Contents

Advertisement

SLOPES AND HIGH SET THRESHOLD
where
T
is a primary system time constant
1
T
is the secondary CT time constant, which can be estimated by the following equation:
2
where
N is the CT ratio
V
is the CT voltage at 10 A exciting current obtained from the CT excitation curve
s
CT limiting factor K
where
I
is the maximum CT primary fault current
p
The figure illustrates the K
CT time-to-saturate (t
K
CT limiting factor, as shown in the figure.
S_LIM
8
Practically, CT time-to-saturate can be obtained by either of the following methods:
Method 1 — Download the "CT Time-to-Saturate Estimator.xlsm" spreadsheet from the GE Multilin web site, located
under Support > Support Documents > B30 Bus Differential System. Enter the required system and CT parameters to
obtain the CT time-to-saturate.
Method 2
Define several time instances t
Use equation 8-5 to calculate the corresponding K
Calculate K
Compare each K
greater than t
8-8
is defined by the following equation:
S_LIM
CT saturation capability curve and K
s
Figure 8-5: Determining CT time-to-saturate
) is determined as a projection of the intersection of the K
SAT
, t
...t
1
2
n
using equation 8-7
S_LIM
value with K
. If K
S
S_LIM
, otherwise it is less than t
i
limiting factor.
S_LIM
, K
...K
S1
S2
Sn
at the given time instance t
S
i
i
B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL
CHAPTER 8: APPLICATION OF SETTINGS
CT saturation capability curve and
s
is less than K
, it means that true t
S_LIM
Eq. 8-6
Eq. 8-7
is
SAT

Advertisement

Table of Contents
loading

Table of Contents