Equipment and cable installation
............................................................................................................................................................................................................................................................

10/100BaseT backplane Ethernet cable installation

Description
This section describes how to connect the 10/100BaseT cables to the Alcatel-Lucent 1665
DMX High-Capacity shelf backplane and route the cables out of the bay and to the
10/100BaseT terminating equipment (for example, a 110/RJ45 punch down block).
Perform this procedure if 10/100BaseT cables are required.
The next section covers installation of Ethernet cables connected directly to SFP modules
on circuit pack faceplates if applicable.
Procedure
Proceed as follows:
........................................................................................................................................................................................................................
1
Refer to the engineering job specification. Obtain the 100BASE-TX Ethernet cables per
Table 1-15, "10/100BaseT Ethernet cable assemblies" (p. 1-60)
group where each cable will be used. Label the cables, indicating bay, shelf and function
group (A, B, C or D) at each end.
........................................................................................................................................................................................................................
2
Connect the function group cables at the Alcatel-Lucent 1665 DMX High-Capacity shelf
end, carefully matching the correct connector with the appropriate backplane connectors
as shown in
"10/100BaseT Ethernet connections" (p.
Note:
maximum of 6.5 in-lb. Do not overtighten.
............................................................................................................................................................................................................................................................
1 - 5 8
Figure 1-18, "10/100BaseT cable installation" (p.
100BASE-TX Ethernet cable retaining screws must be tightened to a
10/100BaseT backplane Ethernet cable installation
1-59). Refer to
1-61).
and note the function
Table 1-16,
365-372-304R7.1
Issue 2 March 2008