Alcatel-Lucent 1665 Dmx High-Capacity Shelf; Cable Requirements And Options - Alcatel-Lucent 1665 Installation Manual

Data multiplexer (dmx)
Hide thumbs Also See for 1665:
Table of Contents

Advertisement

Equipment and cable installation
............................................................................................................................................................................................................................................................
Table 1-1, "Cable requirements and options" (p. 1-5)
Table 1-1 Cable requirements and options
Cable assembly description
Power
Fan
CIT or Cross over LAN Cable
DS1
DS3
TMUX
10/100BaseT Ethernet
Office Alarm
Office Alarm Mult
Miscellaneous Discrete
LAN 10BaseT (Crossover)
LAN 10BaseT (Straight Through)
Sync Timing
Modem
Notes:
1. One -48VA and -48VB main power feeder is required per shelf. Many varieties of 45-amp
connector cables are available as well.
2. One Fan Cable (848839551) is shipped with each Alcatel-Lucent 1665 DMX High-Capacity
shelf.
3. One CIT Cable Assembly or Crossover LAN cable is required for PC interface with the

Alcatel-Lucent 1665 DMX High-Capacity shelf

4. a. One DS1 Cable Assembly is required for each Function unit equipped for 28 DS1 service
(LNW6, LNW7). Each DS1 Cable Assembly consists of two separate cables, both containing
28 pairs of 24 gauge cable. One cable is for input and the other cable is for output.
b.Two DS1 Cable Assemblies are required for each Function unit equipped for 56 DS1 service
(LNW8). Each DS1 Cable Assembly consists of two separate cables, both containing 28 pairs
of 24 gauge cable. One cable is for input and the other cable is for output.
5. a. One DS3 Cable Assembly is required for each Function unit equipped for 12 DS3 service
(LNW16/LNW18). Each orderable code provides two cables One cable consists of 12 inputs
and the other cable consists of 12 outputs. One DS3 Cable Assembly equipped with 24-coax
cables may be used if growth to 48 DS3 packs is planned.
b. Two DS3 Cable Assemblies are required for each Function unit equipped for 48 DS3
............................................................................................................................................................................................................................................................
365-372-304R7.1
Issue 2 March 2008
lists available cables.
Required
See note
Yes
1
Yes
2
Yes
3,
9
Optional
4
Optional
5
Optional
5
Optional
6
Optional
7
Optional
7
Optional
8
Optional
9
Optional
9
Optional
10
Optional
11
(not included with equipment).
Planning
1 - 5