Response Times
Maximum Response Time of the EM 4 F-DO DC24V/2A PROFIsafe
The maximum response time of the EM 4 F-DO DC24V/2A PROFIsafe (without a fault and
when a fault exists) corresponds to the maximum internal conditioning time T
The internal conditioning times of the electronic PM channel depend on the readback time
parameter setting (see table below).
Table D-7
EM 4 F-DO DC24V/2A PROFIsafe (electronic PM channel)
Set Readback
See also
Properties of the 4/8 F-DI 24 VDC PROFIsafe Digital Electronic Module (Page 7-47)
D-4
EM 4 F-DO DC24V/2A PROFIsafe: Internal preparation times
Limit Frequency
Time
1 ms
32.3 Hz
5 ms
28.6 Hz
10 ms
25.0 Hz
50 ms
12.5 Hz
100 ms
7.7 Hz
200 ms
4.3 Hz
400 ms
2.3 Hz
Minimum internal processing
time T
min
4 ms
4 ms
4 ms
4 ms
4 ms
4 ms
4 ms
ET 200S Distributed I/O System - Fail-Safe Modules
Hardware Installation and Operating Manual, 07/2005, A5E00103686-04
.
max
Maximum internal
processing time T
max
16 ms
20 ms
25 ms
55 ms
90 ms
150 ms
300 ms