Siemens SIMATIC ET 200S Installation And Operating Manual page 139

Distributed i/o system - fail-safe modules
Hide thumbs Also See for SIMATIC ET 200S:
Table of Contents

Advertisement

Data for Selecting a Sensor**
Input voltage
Input current
Input delay*
Input characteristic
Connection of 2-wire proximity switch
Time, Frequency
Internal preparation times
Acknowledgment time in safety mode
Minimum sensor signal duration
Protection against Overvoltage
Protection of power supply L+ from surge in
accordance with IEC 61000-4-5 with external
protection elements only
Protection of outputs from surge in accordance
with IEC 61000-4-5 with external protection
elements only
*: With an input delay of 0.5 ms, shielded cable must be used for the digital inputs and the sensor
supply. With 3 ms input delay shielded cables must be used if there is a danger of overvoltage on the
signal lines (see "Electromagnetic Compatibility") to prevent possible passivation of the fail-safe
digital inputs and the sensor power supply switching off. If unshielded signal lines are used the safe
behavior of the process quantities is ensured.
**: For more information on the requirements for sensors and actuators, see "Wiring and Installing
Modules."
ET 200S Distributed I/O System - Fail-Safe Modules
Hardware Installation and Operating Manual, 07/2005, A5E00103686-04
Rated value
For "1" signal
For "0" signal
For "1" signal
For "0" after "1"
For "1" after "0"
Permissible quiescent current
Short-circuit test activated
with input delay of 0.5 ms:
with input delay of 3 ms:
with input delay of 15 ms:
Short-circuit test deactivated
Symmetrical (L+ to M)
Asymmetrical (L+ to PE, M to PE)
Symmetrical (Vs, DI to M)
Asymmetrical (Vs, DI to PE, M to PE)
7.5 4/8 F-DI VDC24V PROFIsafe Digital Electronic Module
Technical Specifications
24 VDC
15 V to 30 V
-30 V to 5 V
3.7 mA, typical
Assignable (for all inputs together)
Typically 0.5 ms
Typically 3 ms
Typically 15 ms
Typically 0.5 ms
Typically 3 ms
Typically 15 ms
In accordance with IEC 1131, Type 1
Not possible
0.6 mA, maximum
Response Times
See
min. 4 ms / max. 7 ms
min. 4 ms / max. 12 ms
min. 4 ms / max. 9 ms
4 ms minimum/6 ms maximum
Table "Minimum Duration of Sensor Signals
See
for Correct Recording by F-DI Module"
and Installing Modules"
+ 1 kV; 1,2/50 μs
+2 kV; 1,2/50 μs
+1 kV; 1,2/50 μs
+1 kV; 1,2/50 μs
Fail-Safe Modules
(0.3 ms to 0.7 ms)
(2.6 ms to 3.4 ms)
(13 ms to 17 ms)
(0.3 ms to 0.7 ms)
(2.6 ms to 3.4 ms)
(13 ms to 17 ms)
"Wiring
in
7-79

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents