7.4.6
Technical Specifications of the PM-D F DC24V PROFIsafe
Overview
Dimensions and Weight
Dimensions W x H x D (mm)
Weight
Data for Specific Module
Number of outputs (P/P switching)
Internal power supply for bus
Assigned address area
•
•
Maximum achievable safety class
•
Fail-safe performance characteristics
•
•
Voltages, Currents, Potentials
Rated supply voltage L+
•
•
•
•
Aggregate current of outputs
•
•
Electrical isolation
•
•
•
•
Permissible potential difference between
•
•
•
ET 200S Distributed I/O System - Fail-Safe Modules
Hardware Installation and Operating Manual, 07/2005, A5E00103686-04
In the I/O area for inputs
In the I/O area for outputs
In accordance with IEC 61508,
DIN VDE 0801, and EN 954
Low demand mode (average probability of
failure on demand)
High demand/continuous mode (probability of
a dangerous failure per hour)
Permissible range
Power loss ride-through of L+
Power loss ride-through of internal P5
Reverse polarity protection
Horizontal installation
Up to 40 °C
–
Up to 60 °C
–
Vertical installation
Up to 40 °C
–
Between channels and backplane bus
Between channels and power supply
Between channels
Between channels/power supply and shield
Shield and ET 200S bus connection
Shield and I/O (SGs, U 1 bus)
ET 200S bus terminal and I/O (SGs, U 1 bus)
7.4 PM-D F DC24V PROFIsafe power module
Technical Specifications
30 x 196.5 x 117.5
Approx. 112 g
6 safety groups (SG 1 through SG 6)
U 1
5 Byte
5 Byte
SIL3, AK6, Category 4
SIL3
< 1,00E-05
< 1,00E-05
24 VDC
21.6 V to 26.4 V
None
5 ms
No
Brief/permanent
10 A/5 A
10 A/4 A
Brief/permanent
10 A/4 A
Yes
No
No
Yes
75 VDC/60 VAC
75 VDC/60 VAC
250 VAC
Fail-Safe Modules
7-45