Properties of the PM-E F pp DC24V PROFIsafe Power Module

Order Number
6ES7 138-4CF41-0AB0
properties
The PM-E F pp 24 VDC PROFIsafe power module has the following properties:
• Two relays for connecting voltage bus P2, 10 A output current
• Relay contacts must be fused externally
• 24 VDC rated load voltage
• Suitable for solenoid valves, DC contactors, and indicator lights
• Suitable for applications for which a grounded configuration is necessary or in which a
• Group fault display (SF; red LED)
• Status display for voltage bus P2 (green LED)
• Status display for load current power supply (PWR; green LED)
• Assignable diagnostics
• For achievable safety classes (safety integrity level), see following table
Table 7-7
PM-E F pp DC24V PROFIsafe
Relay outputs P1
and P2
Switching the P2 Voltage Rail
The power module can switch the P2 voltage rail fail-safe with two series connected relay
contacts in accordance with AK4/SIL2/Cat.3 and AK6/SIL3/Cat.4. P2 is available as P on the
terminal module, P1 as M.
7-24
not-grounded configuration cannot be guaranteed
Overview of Achievable Safety Classes (Safety Integrity Levels) with PM-E F pp DC24V
PROFIsafe
Without standard DO
modules
with standard DO modules
Signal switches
daily or more often
Signal switches
less than once a
day
ET 200S Distributed I/O System - Fail-Safe Modules
Hardware Installation and Operating Manual, 07/2005, A5E00103686-04
Maximum Safety Level That
Can Be Achieved
AK6/ SIL3/Category 4
AK4/ SIL2/ Category 3
AK4/ SIL2/ Category 3