Reaction of F-Modules to Module Failure
The following events occur following a serious internal fault in the F-module causing
F-module failure:
• The connection to the backplane bus is interrupted, and the fail-safe inputs and outputs
• Diagnostics are not transmitted from the F-module, and the "Module Fault" standard
• The SF LED of the corresponding module illuminates.
Specific Information about Diagnostic Functions
All module-specific diagnostic functions, possible causes and their corrective measures are
described in
PROFIsafe Digital Electronic Module"
The status and diagnostic functions indicated by LEDs on the front panel of each F-module
are also presented in these sections.
Reading out Diagnostic Functions
You can display the cause of a fault in the module diagnostics of
Online Help
You can read out diagnostic functions (slave diagnostics) by means of SFC 13 in the
standard user program (see
See also
Diagnostic Functions of PM-D F DC24V PROFIsafe (Page 7-42)
Diagnostic functions of the PM-E F pm DC24V PROFIsafe (Page 7-17)
Diagnostic functions of the PM-E F pp DC24V PROFIsafe (Page 7-32)
Diagnostic Functions of the EM 4/8 F-DI 24 VDC PROFIsafe (Page 7-74)
Diagnostic Functions of the EM 4 F-DO 24 VDC/2 A PROFIsafe (Page 7-90)
ET 200S Distributed I/O System - Fail-Safe Modules
Hardware Installation and Operating Manual, 07/2005, A5E00103686-04
are passivated.
diagnostics message is issued.
"PM-E F pm DC24V PROFIsafe Power Module "
).
.
System and Standard Functions
Diagnostics
5.2 Fault Diagnostics
"4 F-DO DC24V/2A
to
STEP 7
STEP 7
(see
reference manual).
5-7