Siemens SIMATIC ET 200S Installation And Operating Manual page 16

Distributed i/o system - fail-safe modules
Hide thumbs Also See for SIMATIC ET 200S:
Table of Contents

Advertisement

Product Overview
1.3 Using ET 200S Fail-Safe Modules
Using Interface Modules in ET 200S with Fail-Safe Modules
Depending on the F system, select the interface module for ET 200S as follows:
Table 1-1
Interface module
IM151-1 HIGH FEATURE *
for PROFIBUS DP
connection
IM 151-7 F-CPU ** for
PROFIBUS DP connection
IM 151-3 PN HIGH
FEATURE for
PROFINET IO connection
*: V1.1.1 or higher for use with PM-E F pp DC24V PROFIsafe power module
**: V2.0.6 or higher for use with PM-E F pp DC24V PROFIsafe power module
The IM151-1 HIGH FEATURE and the IM 151-3 PN HIGH FEATURE are described in the
ET 200S Distributed I/O System
product information bulletin.
Use in Safety Mode Only
Fail-safe modules can only be used in safety mode. They cannot be used in standard mode.
Achievable Safety Classes
Fail-safe modules are equipped with integrated safety functions for safety mode.
The following safety classes can be achieved in safety mode by assigning appropriate
parameters to the safety functions in
optional package, by combining certain standard and F-modules and by arranging the wiring
of the sensors and actuators in a specific way:
Table 1-2
Safety Class in Safety Mode
In accordance with IEC 61508
SIL2
SIL3
SIL3
See also
Configuring ET 200S with Fail-Safe Modules (Page 2-1)
1-4
Using Interface Modules in ET 200S with Fail-Safe Modules
As of order number
6ES7 151-1BA00-0AB0
6ES7 151-7FA00-0AB0
6ES7 151-3AB00-0AB0
manual; the IM 151-7 F-CPU is described in a separate
Achievable Safety Classes in Safety Mode
In accordance with DIN V 19250 In Accordance with EN 954-1
AK4
AK6
AK6
Hardware Installation and Operating Manual, 07/2005, A5E00103686-04
Can be used in ET 200S
with optional package
S7 Distributed Safety
S7 F Systems
S7 Distributed Safety
S7 Distributed Safety
STEP 7
S7 Distributed Safety
with the
ET 200S Distributed I/O System - Fail-Safe Modules
As of version
V 5.1
V 5.2
V 5.2
V5.4
S7 F Systems
or
Category 3
Category 3
Category 4

Hide quick links:

Advertisement

Table of Contents
loading