Assigning Power Modules to Electronic Modules/Motor Starters
You can use the power modules and electronic modules/motor starters in the following table
within a voltage group.
Note that certain combinations limit the achievable safety classes.
Table 2-3
Assigning Power Modules to Electronic Modules/Motor Starters and Safety Class (Safety Integrity Level)
Power Modules
Reference
PM-E F pm DC24V
"PM-E F pm
PROFIsafe
DC24V PROFI-
safe power
module"
PM-E F pp DC24V
"PM-E F pp
PROFIsafe
DC24V PROFI-
safe power
module"
PM-D F DC24V
"PM-D F
PROFIsafe
DC24V PROFI-
safe power
module"
ET 200S
PM-E DC24V
manual
ET 200S
PM-E DC24..48V
manual
PM-E DC24..48V/
DC24..230V
See also
Properties of the PM-E F pm DC24V PROFIsafe Power Module (Page 7-2)
Properties of the PM-E F pp DC24V PROFIsafe Power Module (Page 7-24)
Properties of the PM-D F DC24V PROFIsafe Power Module (Page 7-37)
ET 200S Distributed I/O System - Fail-Safe Modules
Hardware Installation and Operating Manual, 07/2005, A5E00103686-04
Electronic Module/Motor Starter
Can be used with all standard
electronic modules
Can only be used for:
F-DS1e-x, F-RS1e-x fail-safe motor
•
starters (F-MS)
connection multiplier F-CM
•
PM-D F X1 power/ expansion
•
module
Expansion modules Brake Control xB1
and xB2
Can be used for the F-motor starters
indicated above: Brake Control xB3
and xB4 expansion modules
Can be used with all standard and fail-
safe electronic modules
Can be used with all standard and fail-
safe electronic modules
2.2 Assigning Modules of an ET 200S
Use and Achievable AK/SIL/Category
Safe shutdown of DO
modules from the ET 200S
range
Safe shutdown of motor
starters
Safe shutdown of motor
starters
Supply of F-DI modules and
F-DO modules
Supply of F-DI modules and
F-DO modules
Configuring
AK4/
SIL2/
Category
3
AK6/
SIL3/
Category
4
AK4/
SIL2/
Category
3
AK4/
SIL2/
Category
3
AK6/
SIL3/
Category
4
2-5