Fail-Safe Modules
7.3 PM-E F pp DC24V PROFIsafe power module
Generally Applicable Information on Diagnostics
For information on diagnostics that pertains to all fail-safe modules (for example for reading
out diagnostic functions, passivating channels), refer to
See also
Fault Diagnostics (Page 5-3)
7.3.6
Technical Specifications for the PM-E F pp 24 VDC PROFIsafe
Overview
Dimensions and Weight
Dimensions W x H x D (mm)
Weight
Data for Specific Module
Number of outputs
•
Assigned address area
•
•
Length of cable
•
•
Maximum achievable safety class
•
Fail-safe performance characteristics
•
•
Voltages, Currents, Potentials
Rated supply voltage L+
•
•
•
•
Total current of the relay output
•
7-34
Relay outputs (PP switching)
In the I/O area for inputs
In the I/O area for outputs
Unshielded
Shielded
In accordance with IEC 61508, DIN VDE
0801, and EN 954
Low demand mode (average probability of
failure on demand)
High demand/continuous mode (probability of
a dangerous failure per hour)
Permissible range
Power loss ride-through of L+
Power loss ride-through of internal P5
Reverse polarity protection
Horizontal installation
Up to 40 °C
–
Up to 55 °C
–
Diagnostics
Technical Specifications
30 x 81 x 52
Approx. 80 g
1
5 Byte
5 Byte
200 m, maximum
200 m, maximum
Max. SIL3, AK6, Category 4 (for conditions see
"PM-E F pp DC24V PROFIsafe Power Module")
SIL3
< 1,00E-05
< 1,00E-05
24 VDC
20.4 V to 28.8 V
None
5 ms
No
10 A
8 A
ET 200S Distributed I/O System - Fail-Safe Modules
Hardware Installation and Operating Manual, 07/2005, A5E00103686-04
.