Response Times Of Em 1 F-Ro Dc24V/5A Ac24 - Siemens SIMATIC ET 200S Installation And Operating Manual

Distributed i/o system - fail-safe modules
Hide thumbs Also See for SIMATIC ET 200S:
Table of Contents

Advertisement

Digital Electronics Module 1 F-RO DC24V/5A AC24..230V/5A
2.7 Response Times of EM 1 F-RO DC24V/5A AC24..230V/5A
Switching capacity and service life of the contacts
The following table indicates the switching capacity and service life of the contacts. Service
life can be increased beyond the value indicated in the following table by using an external
protective element.
Table 2-4
For resistive load
For inductive load
according to IEC 947-
5-1 DC 13/ AC15
2.7
Response Times of EM 1 F-RO DC24V/5A AC24..230V/5A
2.7
Maximum response times of EM 1 F-RO DC24V/5A AC24..230V/5A
The maximum response time of EM 1 F-RO DC24V/5A AC24..230V/5A (under error free
circumstances and during the presence of errors) is the sum of:
• The maximum response time of the fail-safe output, used for activating the F-RO-module
• The switching time or the relay release time of the F-RO-module (refer to the Technical
2-12
Switching capacity and service life of the contacts
Resistance load
DC 24 V
AC 230 V
DC 24 V
AC 230 V
(e.g. EM 4F-DO DC24V/2A PROFIsafe; refer to the manual, Appendix D) and
Specifications, Chapter
Product Information for the Distributed I/O System ET 200S, Fail-Safe Systems Manual
Voltage
Current
5.0 A
3.0 A
2.0 A
1.0 A
0.5 A
5.0 A
3.0 A
2.0 A
1.0 A
0.5 A
1.0 A
0.5 A
1.0 A
0.5 A
2.6
).
Duty cycle (avg.) contacting element
0.35 million
0.5 million
0.75 million
1.8 million
4 million
0.1 million
0.15 million
0.2 million
0.4 million
0.8 million
0.1 million
0.2 million
0.2 million
0.35 million
Product information, 07/2006, A5E00825271-01