Cables - Siemens SITRANS LUT400 Operating Instructions Manual

Ultrasonic controllers
Hide thumbs Also See for SITRANS LUT400:
Table of Contents

Advertisement

The SITRANS LUT400 is available in AC or DC power models.
AC Power
12
L1
100 230 V
AC: 100-230 V AC ±15%, 50/60 Hz, 36 VA (10W)
Note: Make sure device is connected to a reliable ground.
1.
To wire for power, strip the cable jacket for approximately 70 mm (2.75") from the end
of the cable, and thread the wires through the gland
2.
Connect the wires to the terminals as shown: the polarity is identified below the
terminal block.
3.
Ground the device according to local regulations.
Notes for AC power connections:
• The equipment must be protected by a 15 A fuse, or circuit breaker on all
current-carrying conductors in the building installation.
• A circuit breaker or switch in the building installation, marked as the disconnect
switch, must be in close proximity to the equipment and within easy reach of the
operator, and must disconnect all current-carrying conductors.

Cables

The SITRANS LUT400 is designed to work with two conductor shielded transducer
cables.
Connection
mA output, sync,
Temperature sensor,
discrete input
Transducer
Relay output
AC input
a. Preferred shielding is braided shield.
1. If cable is routed through conduit, use only approved suitable-size hubs for waterproof
applications.
Page 22
SITRANS LUT400 (HART) – OPERATING INSTRUCTIONS
INPUT
POWER
13
14
L2/N
2 copper conductors, twisted, with shield
2
0.823 mm
(22 - 18 AWG)
Maximum length: 365 m
Shielded two-wire. Maximum length: 365 m
Warning: Do not use a coaxial transducer cable
extension with the SITRANS LUT400. High voltage
transmitted on shield of coaxial cable could result in
personal injury, damage to equipment, or poor device
performance.
Copper conductors per local requirements.
DC Power
INPUT
POWER
12
13
10 32 V
DC: 10-32 V DC, 10W
1
.
Cable Type
a
/drain wire, 300V 0.324 -
.
14
A5E33329501