Setting The Pump Start Delays - Siemens SITRANS LUT400 Operating Instructions Manual

Ultrasonic controllers
Hide thumbs Also See for SITRANS LUT400:
Table of Contents

Advertisement

Example:
Pump 1 is set to pump for an extra 60 seconds every 5 hours, pump 2 should not run-on.
Parameter
2.7.2.3.2. Run-On Interval
2.7.2.3.3. Run-On Duration
Pump 1
2.7.2.3.4. Run-On Duration
Pump 2

Setting the pump start delays

In the event that power to the SITRANS LUT400 has been lost, the pump start delay
ensures that all of the pumps do not start at once to avoid power surges. There are two
parameters used here: Pump Start Delay and Power Resumption Delay.
Example:
The delay between pumps is set to 20 seconds and the delay of the first pump is set to 60
seconds.
Parameter
2.7.2.4. 1 . Delay Between
Starts
2.7.2.4.2. Power Resumption
Delay
A5E33329501
Sample
Value
5
60
0
Sample
Value
20
60
SITRANS LUT400 (HART) – OPERATING INSTRUCTIONS
Description
Five hours between pump run-on occurrences.
The pump will run-on for 60 seconds.
Pump 2 will never run-on.
Description
Wait at least 20 seconds between pump starts.
Wait for 60 seconds when power is restored for
the first pump to activate.
Page 89