Application Examples; Level Application Example - Siemens SITRANS LUT400 Operating Instructions Manual

Ultrasonic controllers
Hide thumbs Also See for SITRANS LUT400:
Table of Contents

Advertisement

Application examples

In the examples that follow, substitute your own application details. If the examples do
not apply to your application, check the applicable parameter reference for the available
options.

Level Application Example

distance
8.5 m
Quick Start Parameter
Transducer
Operation
Temperature Source
Units
High Calibration Point
Low Calibration Point
Response Rate
a.
Fill Rate per Minute 2.3.1.
See
The application is a vessel that takes an average 3 hours (180 minutes) to fill and 3 weeks
to empty.
Fill rate = (Low Cal Pt. – High Cal Pt.) / fastest of fill or empty time
= (15.5 m – 1 m) / 180 min.
= 14.5 m /180 min. = 0.08 m/min.
Page 58
SITRANS LUT400 (HART) – OPERATING INSTRUCTIONS
1.0 m
High Cal. Point
space
7.5 m
level
6.5 m
Setting
Description
XPS-15
Transducer to be used with the LUT400.
LEVEL
Material level referenced from Low Cal. Point.
TS-3
Temperature source.
M
Sensor measurement units.
1.0
Process full level.
15.0
Process empty level.
SLOW
Sets Fill Rate
on page 142.
sensor reference point
15.0 m
Low Cal. Point
Far Range
a
/ Empty Rate to 0.1 m/minute.
7ML1998MV01

Advertisement

Table of Contents
loading

Table of Contents