Siemens SITRANS LUT400 Operating Instructions Manual page 207

Ultrasonic controllers
Hide thumbs Also See for SITRANS LUT400:
Table of Contents

Advertisement

2.16.1. Daily Totalizer
Read only. Current daily totalizer value. (Automatically resets daily and can be
reset by user.)
Values
2.16.2. Running Totalizer
Read only. Current running totalizer value. (Reset only by user.)
Values
2.16.3. Totalizer Decimal Position
Sets the maximum number of decimal places to be displayed.
Options
2.16.4. Totalizer Multiplier
Use this feature if the LCD Total increments by an amount that is too large (or
too small).
Options
Enter the factor (powers of 10 only) by which actual flow is divided, prior to
display on LCD. Use a value such that the eight-digit totalizer doesn't roll over
between readings.
Example: For an LCD Total display in 1000s of flow units, enter
2.16.5. Reset Daily Totalizer
Select YES to reset daily totalizer value to zero.
Options
A5E33329501
SITRANS LUT400 (HART) – OPERATING INSTRUCTIONS
Range: 0.00 to 999999999
Default: 0.00
Range: 0.00 to 999999999
Default: 0.00
NO DIGITS
no digits after the decimal point
1 DIGIT
1 digit after the decimal point
*
2 DIGITS
2 digits after the decimal point
3 DIGITS
3 digits after the decimal point
.001
.01
.1
*
1
10
100
1000
10,000
100,000
1,000,000
10,000,000
*
NO
YES
1000.
Page 199