Siemens SITRANS LUT400 Operating Instructions Manual page 148

Ultrasonic controllers
Hide thumbs Also See for SITRANS LUT400:
Table of Contents

Advertisement

2.1.6. Transducer
Specifies the Siemens transducer connected to the device.
Options
Notes:
• When Transducer (2.1.6.) is set to NO TRANSDUCER, the LOE fault will
display immediately.
• An Echo Profile (3.2.1.) cannot be requested from LUI when Transducer
(2.1.6.) is set to NO TRANSDUCER. The local push button will not operate.
2.1.7. Frequency
Adjust the shot transmit pulse frequency (in kHz).
Values
2.1.8. Long Shot Duration
Adjust the duration of the long shot transmit pulse (in μs).
Values
2.1.9. Short Shot Duration
Adjust the duration of the short shot transmit pulse (in μs).
Values
2.2. Calibration
2.2.1. Low Calibration Point
Distance from sensor reference point
(2.1.1.)
Values
1.
The point from which level measurement is referenced (see Sensor Mode on page 138 for illus-
tration).
Page 140
SITRANS LUT400 (HART) – OPERATING INSTRUCTIONS
*
NO TRANSDUCER
XRS-5
XPS-10
XPS-15
XCT-8
XCT-12
XPS-30
XPS-40
XLT-30
XLT-60
STH
Range: 10.000 to 52.000
Default: Depends on transducer selected in
Range: 100.000 to 2000.000
Default: Depends on transducer selected in
Range: 100.000 to 2000.000
Default: Depends on transducer selected in
.
Range: 0.000 to 60.000
Default: 60.000
Transducer (2.1.6.).
Transducer (2.1.6.).
Transducer (2.1.6.).
1
to Low Calibration Point defined in Units
A5E33329501