Connecting Shielded Cables Via A Shield Connecting Element - Siemens SIMOTION C 230-2 Operating Instructions Manual

Hide thumbs Also See for SIMOTION C 230-2:
Table of Contents

Advertisement

3. Remove a sufficient length of the cable sheath at the control end so that you can connect the
shield to the shield connecting element and the free cable ends to the front connector.
4. Wire the signal line to the front connector.
Figure 6-17
Note
For the assignment of the front connector and the description of the I/O interface, refer to
chapter I/O interface (Page 70).
Connection of additional actuators/encoders
If you wish to connect additional actuators/encoders to the SMs on the I/O bus, proceed in the
same way as for connecting digital inputs/digital outputs to the SIMATIC S7-300.
See the S7-300, M7-300 Automation Systems, Module Data Manual.
The digital inputs/digital outputs on the central I/O system are recorded/output at a refresh rate
of approx. 1 ms.
6.1.8

Connecting shielded cables via a shield connecting element

Application
With the shield connecting element, you can easily connect all the shielded wires of the
SIMOTION C or S7 modules to ground by directly connecting the shield connecting element with
the mounting rail.
SIMOTION C
Operating Instructions, 11/2022, A5E33441428B
Overview of connections for measuring inputs or proximity encoders
Connecting
6.1 Wiring
117

Advertisement

Table of Contents
loading

This manual is also suitable for:

Simotion c240Simotion c240 pn

Table of Contents