6.11.3 Settings

Addr.
Setting Title
3001
Sens. Earth Flt
3002
3U0>
3003
Uph-e min
3004
Uph-e max
3005
3I0>
3006
T Sens.E/F
3007
T 3U0>
3008A
TRIP Direction
3010
CT Err. I1
3011
CT Err. F1
3012
CT Err. I2
3013
CT Err. F2
7SA6 Manual
C53000-G1176-C133-1
(UU ) (address ) of the c.t. with its associated current &7 (UU , (address
) as well as a further c.t. operating point &7 (UU )/&7 (UU , (address
 and ), above which the angle displacement remains practically constant
(see Figure 6-92), are set. The relay then approximates, with adequate accuracy, the
characteristic of the transformer. In isolated networks this angle error compensation is
not necessary.
∆ϕ
,
)
)
Figure 6-92
Settings for the phase angle correction
Note: The indicated secondary current values refer to current input I
independent from the nominal value of the device.
Setting Options
Alarm Only
ON
OFF
1..150 V
10..100 V
10..100 V
0.003..1.000 A
0.00..320.00 sec; Ø
0.00..320.00 sec; Ø
Forward
Reverse
Non-Directional
0.003..1.600 A
0.0..5.0 °; Ø
0.003..1.600 A
0.0..5.0 °; Ø
Default Setting
Alarm Only
Sensitive Earth Flt.(comp/ isol.
starp.)
50 V
3U0> pickup
40 V
Uph-e min of faulted phase
75 V
Uph-e max of healthy phases
0.050 A
3I0> Release directional ele-
ment
1.00 sec
Time delay for sens. E/F detec-
tion
0.00 sec
Time delay for sens. E/F trip
Forward
Direction for sens. E/F trip
0.050 A
Current I1 for CT Angle Error
0.0 °
CT Angle Error at I1
1.000 A
Current I2 for CT Angle Error
0.0 °
CT Angle Error at I2
Functions
,
I
. They are
4
Comments
6-165