Information Overview - Siemens siprotec 7SA6 User Manual

Distance protection
Hide thumbs Also See for siprotec 7SA6:
Table of Contents

Advertisement

Addr.
Setting Title
3538
MC Usyn< Uline<
3539
MC O/RIDE

6.13.4 Information Overview

F.No.
Alarm
2901
>Sync. on
2902
>Sync. off
2903
>BLOCK Sync.
2906
>Sync. Start
2907
>Sync. synch
2908
> Usyn< U-line>
2909
> Usyn> U-line<
2910
> Usyn< U-line<
2911
>Sync. o/ride
2930
Sync. on/off BI
2931
Sync. OFF
2932
Sync. BLOCK
2934
Sync. faulty
2935
Sync.Tsup.Exp
2941
Sync. running
2942
Sync.Override
2943
Synchronism
2944
Usyn< U-line>
2945
Usyn> U-line<
2946
Usyn< U-line<
2947
Sync. Udiff>
7SA6 Manual
C53000-G1176-C133-1
Setting Options
YES
NO
YES
NO
Important information available as output by the device is explained, in so far as it can
not be interpreted in the following list and was not described in the foregoing text.
"!6\QF6WDUW" (F.No. 2906)
Request to execute a check synchronism measurement from an external automatic
reclosure device. After this request, the conditions for automatic reclosure are
checked.
"6\QF UHOHDVH" (F.No. 2951)
Release signal to an external automatic reclosure device.
.
>Switch on synchro-check function
>Switch off synchro-check function
>BLOCK synchro-check function
>Start synchro-check
>Sync-Prog. Live bus / live line / Sync
>Sync-Prog. Dead bus / live line
>Sync-Prog. Live bus / dead line
>Sync-Prog. Dead bus / dead line
>Sync-Prog. Override ( bypass )
Synchro-check ON/OFF via BI
Synchro-check is switched OFF
Synchro-check is BLOCKED
Synchro-check function faulty
Synchro-check supervision time expired
Synchronization is running
Synchro-check override/bypass
Synchronism detected
Sync. dead bus / live line detected
Sync. live bus / dead line detected
Sync. dead bus / dead line detected
Sync. Voltage diff. greater than limit
Default Setting
NO
Dead bus / dead line check
before Man.Cl
NO
Override of any check before
Man.Cl
Comments
Functions
Comments
6-205