Siemens siprotec 7SA6 User Manual page 740

Distance protection
Hide thumbs Also See for siprotec 7SA6:
Table of Contents

Advertisement

Appendix
Addr.
Setting Title
3437
ADT SynRequest
3438
T U-stable
3440
U-live>
3441
U-dead<
3450
1.AR: START
3451
1.AR: T-ACTION
3453
1.AR Tdead 1Flt
3454
1.AR Tdead 2Flt
3455
1.AR Tdead 3Flt
3456
1.AR Tdead1Trip
3457
1.AR Tdead3Trip
3458
1.AR: Tdead EV.
3459
1.AR: CB? CLOSE
3460
1.AR SynRequest
3461
2.AR: START
3462
2.AR: T-ACTION
3464
2.AR Tdead 1Flt
3465
2.AR Tdead 2Flt
3466
2.AR Tdead 3Flt
3467
2.AR Tdead1Trip
3468
2.AR Tdead3Trip
3469
2.AR: Tdead EV.
3470
2.AR: CB? CLOSE
3471
2.AR SynRequest
3472
3.AR: START
3473
3.AR: T-ACTION
3475
3.AR Tdead 1Flt
3476
3.AR Tdead 2Flt
B-16
Function
Setting Options
Automatic Reclo-
YES
sure
NO
Automatic Reclo-
0.10..30.00 sec
sure
Automatic Reclo-
30..90 V
sure
Automatic Reclo-
2..70 V
sure
Automatic Reclo-
YES
sure
NO
0.01..300.00 sec; ∞
Automatic Reclo-
sure
0.01..1800.00 sec; ∞
Automatic Reclo-
sure
0.01..1800.00 sec; ∞
Automatic Reclo-
sure
0.01..1800.00 sec; ∞
Automatic Reclo-
sure
0.01..1800.00 sec; ∞
Automatic Reclo-
sure
0.01..1800.00 sec; ∞
Automatic Reclo-
sure
Automatic Reclo-
0.01..1800.00 sec
sure
Automatic Reclo-
YES
sure
NO
Automatic Reclo-
YES
sure
NO
Automatic Reclo-
YES
sure
NO
0.01..300.00 sec; ∞
Automatic Reclo-
sure
0.01..1800.00 sec; ∞
Automatic Reclo-
sure
0.01..1800.00 sec; ∞
Automatic Reclo-
sure
0.01..1800.00 sec; ∞
Automatic Reclo-
sure
0.01..1800.00 sec; ∞
Automatic Reclo-
sure
0.01..1800.00 sec; ∞
Automatic Reclo-
sure
Automatic Reclo-
0.01..1800.00 sec
sure
Automatic Reclo-
YES
sure
NO
Automatic Reclo-
YES
sure
NO
Automatic Reclo-
YES
sure
NO
0.01..300.00 sec; ∞
Automatic Reclo-
sure
0.01..1800.00 sec; ∞
Automatic Reclo-
sure
0.01..1800.00 sec; ∞
Automatic Reclo-
sure
Default Setting
NO
Request for synchro-check after 3pole
AR
0.10 sec
Supervision time for dead/ live voltage
48 V
Voltage threshold for live line or bus
30 V
Voltage threshold for dead line or bus
YES
Start of AR allowed in this cycle
0.20 sec
Action time
1.20 sec
Dead time after 1phase faults
1.20 sec
Dead time after 2phase faults
0.50 sec
Dead time after 3phase faults
1.20 sec
Dead time after 1pole trip
0.50 sec
Dead time after 3pole trip
1.20 sec
Dead time after evolving fault
NO
CB ready interrogation before reclos-
ing
NO
Request for synchro-check after 3pole
AR
NO
AR start allowed in this cycle
0.20 sec
Action time
1.20 sec
Dead time after 1phase faults
1.20 sec
Dead time after 2phase faults
0.50 sec
Dead time after 3phase faults
∞ sec
Dead time after 1pole trip
0.50 sec
Dead time after 3pole trip
1.20 sec
Dead time after evolving fault
NO
CB ready interrogation before reclos-
ing
NO
Request for synchro-check after 3pole
AR
NO
AR start allowed in this cycle
0.20 sec
Action time
1.20 sec
Dead time after 1phase faults
1.20 sec
Dead time after 2phase faults
Comments