Information Overview - Siemens siprotec 7SA6 User Manual

Distance protection
Hide thumbs Also See for siprotec 7SA6:
Table of Contents

Advertisement

Functions
Addr.
Setting Title
2624
I> Telep/BI
2625
I> SOTF
2640
Ip>
2642
T Ip Time Dial
2643
Time Dial TD Ip
2646
T Ip Add
2650
3I0p PICKUP
2652
T 3I0p TimeDial
2653
TimeDial TD3I0p
2656
T 3I0p Add
2660
IEC Curve
2661
ANSI Curve
2670
I(3I0)p Tele/BI
2671
I(3I0)p SOTF
2630
Iph> STUB
2631
T Iph STUB
2632
3I0> STUB
2633
T 3I0 STUB
2634
I-STUB Telep/BI
2635
I-STUB SOTF
6.9.4

Information Overview

F.No.
Alarm
7104
>BLOCK O/C I>>
7105
>BLOCK O/C I>
6-154
Setting Options
NO
YES
NO
YES
0.10..4.00 A; ∞
0.05..3.00 sec; ∞
0.50..15.00; ∞
0.00..30.00 sec
0.05..4.00 A; ∞
0.05..3.00 sec; ∞
0.50..15.00; ∞
0.00..30.00 sec
Normal Inverse
Very Inverse
Extremely Inverse
Long time inverse
Inverse
Short Inverse
Long Inverse
Moderately Inverse
Very Inverse
Extremely Inverse
Definite Inverse
NO
YES
NO
YES
0.10..25.00 A; ∞
0.00..30.00 sec; ∞
0.05..25.00 A; ∞
0.00..30.00 sec; ∞
NO
YES
NO
YES
>BLOCK Backup OverCurrent I>>
>BLOCK Backup OverCurrent I>
Default Setting
NO
Instantaneous trip via Teleprot./
BI
NO
Instantaneous trip after Switch-
OnToFault
∞ A
Ip> Pickup
0.50 sec
T Ip Time Dial
5.00
Time Dial TD Ip
0.00 sec
T Ip Additional Time Delay
∞ A
3I0p Pickup
0.50 sec
T 3I0p Time Dial
5.00
Time Dial TD 3I0p
0.00 sec
T 3I0p Additional Time Delay
Normal Inverse
IEC Curve
Inverse
ANSI Curve
NO
Instantaneous trip via Teleprot./
BI
NO
Instantaneous trip after Switch-
OnToFault
1.50 A
Iph> STUB Pickup
0.30 sec
T Iph STUB Time delay
0.20 A
3I0> STUB Pickup
2.00 sec
T 3I0 STUB Time delay
NO
Instantaneous trip via Teleprot./
BI
NO
Instantaneous trip after Switch-
OnToFault
Comments
Comments
7SA6 Manual
C53000-G1176-C133-1