6.2.4

Distance Protection with Polygonal Tripping Characteristic

6.2.4.1

Method of Operation

Operating
Polygons
6-54
DistanceTime Out Forward PICKUP
DistanceTime Out Reverse/Non-dir. PICKUP
Distance protection: General trip
Distance TRIP command - Only Phase L1
Distance TRIP command - Only Phase L2
Distance TRIP command - Only Phase L3
Distance TRIP command Phases L123
Distance TRIP single-phase Z1
DisTRIP 3phase in Z1 with single-ph Flt.
DisTRIP 3phase in Z1 with multi-ph Flt.
Distance TRIP single-phase Z1B
DisTRIP 3phase in Z1B with single-ph Flt
DisTRIP 3phase in Z1B with multi-ph Flt.
Distance TRIP single-phase Z2
Distance TRIP 3phase in Z2
Distance TRIP 3phase in Z3
Distance TRIP 3phase in Z4
Distance TRIP 3phase in Z5
DisTRIP Z1B with Teleprotection scheme
Dist.: Trip by fault detection, forward
Dist.: Trip by fault detec, rev/non-dir.
A tripping characteristic in the shape of a polygon is defined for each of the distance
zones. In total, there are five independent zones and one additional controlled zone
for each fault impedance loop. In Figure 6-29 the shape of a polygon is illustrated. The
first zone is shaded and forward directional, the third zone is reverse directional.
In general, the polygon is defined by means of a parallelogram which intersects the
axes with the values R and X as well as the tilt ϕ
und ϕ
R
may be used to cut the area of the load impedance out of the polygon.
Load
Load
The axial coordinates can be set individually for each zone; ϕ
common for all zones. The parallelogram is symmetrical with respect to the origin of
the R–X–coordinate system; the directional characteristic however limits the tripping
range to the desired quadrants (refer to "Direction Determination" below).
Comments
. A load trapezoid with the setting
Line
, R
Line
Load