Measures For Weak Or Zero Infeed - Siemens siprotec 7SA6 User Manual

Distance protection
Hide thumbs Also See for siprotec 7SA6:
Table of Contents

Advertisement

6.6.1.5

Measures for Weak or Zero Infeed

Echo Function
7SA6 Manual
C53000-G1176-C133-1
EF Telep. off
1313 >EF TeleprotBLK
EF Pickup
&
EF forward
Figure 6-77
Transient blocking for a
schemes
On lines where there is only a single sided infeed or where the system starpoint is only
earthed behind one line end, the line end without zero sequence current cannot
generate a permissive signal, as fault detection does not take place there. With the
comparison schemes, using a permissive signal, fast tripping could not even be
achieved at the line end with strong infeed without special measures, as the end with
weak infeed does not transmit a permissive release signal.
To achieve rapid tripping at both line ends under these conditions, the device has a
special supplement for lines with weak zero sequence current infeed.
To enable even the line end with the weak infeed to trip, 7SA6 provides a weak infeed
tripping supplement. As this is a separate protection function with a dedicated trip
command, it is described in a separate section (6.7).
Figure 6-78 shows the method of operation of the echo function. It may be switched in
address  )&7 :HDN ,QIHHG (Weak Infeed MODE) to be activated ((&+2
RQO\) or to be deactivated (2))). By means of this "switch" the weak infeed tripping
function can also be activated ((&+2 DQG 75,3, refer also to Section 6.7). This
setting is common to the teleprotection function for the distance protection and for the
earth fault protection.
The received signal at the line end that has no earth current is returned to the other
line end as an "echo" by the echo function. The received echo signal at the other line
end enables the release of the trip command.
The detection of the weak infeed condition and accordingly the requirement for an
echo are combined in the central AND gate (Figure 6-78). The earth fault protection
must neither be switched off nor blocked, as it would otherwise always produce an
echo due to the missing fault detection.
The essential condition for an echo is the absence of an earth current (current stage
,R0LQ 7HOHSURW) with the simultaneous reception signal from the teleprotection
scheme logic, as shown in the corresponding logic diagrams (Figure 6-72 or 6-74).
To prevent the generation of an echo signal after the line has been tripped and the
earth current stage ,R0LQ 7HOHSURW has reset, it is not possible to generate an
echo if a fault detection by the earth current stage had already been present (RS flip-
flop in Figure 6-78). In any event, the echo may be blocked at any time via the binary
input „!() %ON(FKR".
If the conditions for an echo signal are met, a short delay 7ULS(FKR '(/$< is
initially activated. This delay is necessary to avoid transmission of the echo if the
protection at the weak line end has a longer fault detection time during reverse faults
or if it picks up a little later due to unfavourable fault current distribution. If however the
≥1
"!( U…7yxÃXhv‡ÃUv€r
T
T
"!  U…7yxÃ7y‚pxUv€r
directional comparison and directional unblocking
Functions
&
1386
EF TeleTransBlk
transient
blocking
Figure 6-72
or 6-74
6-129