External Direct And Remote Tripping - Siemens siprotec 7SA6 User Manual

Distance protection
Hide thumbs Also See for siprotec 7SA6:
Table of Contents

Advertisement

Technical Data
10.8

External Direct and Remote Tripping

External Trip of the
Local Breaker
10-24
Operating time, total
Trip time delay
Time expiry tolerance
The set time is a pure delay time.
approx. 11 ms
0.00 s to 30.00 s, ∞
or ∞ (ineffective)
1 % of set value or 10 ms
(steps 0.01 s)
7SA6 Manual
C53000-G1176-C133-1

Hide quick links:

Advertisement

Table of Contents
loading