Troubleshooting

o
o
o
o
o
7SA6 Manual
C53000-G1176-C133-1
If a device reports a problem or failure, the procedure below is recommended.
If none of the LEDs on the front panel are lit, then verify:
Are the printed circuit boards put into the correct slots and properly covered by the
front panel?
Are the plug connectors of the flat cable plugged into the printed circuit boards and do
the lockings snap properly?
Is the auxiliary voltage high enough? Is the polarity at the corresponding connections
correct?
Are the voltage magnitude and polarity correct for the power supply. Connection draw-
ings are shown in Section A.2 of Appendix A?
Has the fuse in the power supply not blown? The location of the fuse is shown in Fig-
ure 9-7. If the fuse needs to be replaced, see Subsection 9.5.2.
If the red "ERROR" LED is on and the green "RUN" LED is off, then the device has
recognized an internal fault. Re-initializing the device can be attempted, see Section
9.2.
If you see the following display, the device has arrived "monitor"-mode. In this case
you may initialize the device via DIGSI
021,725

(TXLSPHQW GDWD ²!
8VHU LQWHUIDFH ²!
6\VWHP ,IDFH
²!
5HVHW
²!
6LHPHQV LQVWHQ ²!
Figure 9-3
Monitor annunciation in device display
q
Connect the operating interface of the SIPROTEC
terface of the SIPROTEC
q
Select ,QLWLDOL]H GHYLFH in the menu 'HYLFH (Figure 9-4).
Initializing device via
Figure 9-4
®
4:






®
4 device and open the DIGSI
®
DIGSI
4
Routine Checks and Maintenance
®
4 device with the operating in-
®
4 software program.
9-9