Siemens siprotec 7SA6 User Manual page 729

Distance protection
Hide thumbs Also See for siprotec 7SA6:
Table of Contents

Advertisement

Addr.
Setting Title
1103
FullScaleVolt.
1104
FullScaleCurr.
1105
Line Angle
1110
x'
1111
Line Length
1112
x'
1113
Line Length
1116
RE/RL(Z1)
1117
XE/XL(Z1)
1118
RE/RL(Z1B...Z5)
1119
XE/XL(Z1B...Z5)
1120
K0 (Z1)
1121
Angle K0(Z1)
1122
K0 (> Z1)
1123
AngleI K0(> Z1)
1126
RM/RL ParalLine
1127
XM/XL ParalLine
1128
RATIO Par. Comp
1130A
PoleOpenCurrent
1131A
PoleOpenVoltage
1132A
SI Time all Cl.
1134
Line Closure
1135
Reset Trip CMD
1140A
I-CTsat. Thres.
1150A
SI Time Man.Cl
7SA6 Manual
C53000-G1176-C133-1
Function
Setting Options
Power System Data
1.0..1200.0 kV
2
Power System Data
10..5000 A
2
30..89 °
Power System Data
2
Power System Data
0.005..6.500 Ohm / km
2
Power System Data
1.0..1000.0 km
2
Power System Data
0.005..10.000 Ohm / mile
2
Power System Data
0.6..650.0 Miles
2
Power System Data
-.33..7.00
2
Power System Data
-.33..7.00
2
Power System Data
-.33..7.00
2
Power System Data
-.33..7.00
2
Power System Data
0.000..4.000
2
-135.00..135.00 °
Power System Data
2
Power System Data
0.000..4.000
2
-135.00..135.00 °
Power System Data
2
Power System Data
0.00..8.00
2
Power System Data
0.00..8.00
2
Power System Data
50..95 %
2
Power System Data
0.05..1.00 A
2
Power System Data
2..70 V
2
Power System Data
0.01..30.00 sec
2
Power System Data
Manual Close BI only
2
Current OR Voltage or Man-
ual close BI
CBaux OR Current or Man-
ual close BI
Current flow or Manual close
BI
Power System Data
with Pole Open Current
2
Threshold only
with CBaux AND Pole Open
Current
0.2..50.0 A; ∞
Power System Data
2
Power System Data
0.01..30.00 sec
2
Default Setting
400.0 kV
Measurement: Full Scale Voltage
(100%)
1000 A
Measurement: Full Scale Current
(100%)
85 °
Line Angle
0.150 Ohm / km
x' - Line Reactance per length unit
100.0 km
Line Length
0.242 Ohm / mile
x' - Line Reactance per length unit
62.1 Miles
Line Length
1.00
Zero seq. comp. factor RE/RL for Z1
1.00
Zero seq. comp. factor XE/XL for Z1
1.00
Zero seq. comp.factor RE/RL for
Z1B...Z5
1.00
Zero seq. comp.factor XE/XL for
Z1B...Z5
1.000
Zero seq. comp. factor K0 for zone Z1
0.00 °
Zero seq. comp. angle for zone Z1
1.000
Zero seq.comp.factor K0,higher zones
>Z1
0.00 °
Zero seq. comp. angle, higher zones
>Z1
0.00
Mutual Parallel Line comp. ratio RM/
RL
0.00
Mutual Parallel Line comp. ratio XM/XL
85 %
Neutral current RATIO Parallel Line
Comp
0.10 A
Pole Open Current Threshold
30 V
Pole Open Voltage Threshold
0.05 sec
Seal-in Time after ALL closures
Manual Close BI only
Recognition of Line Closures with
with Pole Open Current
RESET of Trip Command
Threshold only
10.0 A
CT Saturation Threshold
0.30 sec
Seal-in Time after MANUAL closures
Appendix
Comments
B-5