Siemens siprotec 7SA6 User Manual page 224

Distance protection
Hide thumbs Also See for siprotec 7SA6:
Table of Contents

Advertisement

Functions
Phase–Earth Loops
6-42
U
L1–E
U
L2–E
Figure 6-22
Short circuit of a phase-phase loop
The calculation of the phase-phase loop does not take place as long as one of the
concerned phases is switched off (during single-pole dead time), to avoid an incorrect
measurement with the undefined measured values existing during this state. A state
recognition (refer to Section 6.20) provides the corresponding block signal. A logic
block diagram of the phase-phase measuring system is shown in Figure 6-23.
U
Lx
U
Ly
I
Lx
I
Ly
!! Dƒu3
I
>
Lx
>
I
from state
Ly
recognition
Figure 6-23
Logic of the phase-phase measuring system
For the calculation of the phase-earth loop, for example during a L3–E short-circuit
(Figure 6-24) it must be noted that the impedance of the earth return path does not
correspond to the impedance of the phase. In the loop equation
I
Z
I
Z
=
U
L3
L
E
E
Z
is replaced by (Z
/Z
E
E
Z
E
Z
Z
------ -
I
I
L3
L
E
L
Z
L
From this the line impedance can be extracted
U
L3–E
Z
----------------------------------------- -
=
L
Z
Z
I
I
L3
E
L
Z
I
L1
L
Z
I
L
L2
Measuring
System
L
–L
x
y
&
L3–E
)·Z
and the result is:
L
L
U
=
L3–E
E
L1
L2
L3
E
R
; X
x–y
x–y
7SA6 Manual
C53000-G1176-C133-1