4 How to Program
Bahasa Indonesia
[99]
Unknown
1-20 Motor Power [kW]
Range:
Application
[Application dependant]
dependent*
4
Application
[Application dependant]
dependent*
1-22 Motor Voltage
Range:
Application
[Application dependant]
dependent*
1-23 Motor Frequency
Range:
Application
[20 - 1000 Hz]
dependent*
1-24 Motor Current
Range:
Application
[Application dependant]
dependent*
NOTE!
This parameter cannot be adjusted while the motor is running.
1-25 Motor Nominal Speed
Range:
Application
[100 - 60000 RPM]
dependent*
4-4
Part of Language package 2
Function:
Enter the nominal motor power in kW according to the motor nameplate data. The default value
corresponds to the nominal rated output of the unit.
This parameter cannot be adjusted while the motor is running. This parameter is visible in LCP if
Regional Settings
International
par. 0-03
is
NOTE!
Four sizes down, one size up from nominal unit rating.
Function:
Enter the nominal motor voltage according to the motor nameplate data. The default value corre-
sponds to the nominal rated output of the unit.
This parameter cannot be adjusted while the motor is running.
Function:
Min - Max motor frequency: 20–1000 Hz.
Select the motor frequency value from the motor nameplate data. If a value different from 50 Hz
or 60 Hz is selected, it is necessary to adapt the load independent settings in par. 1-50
Magnetization at Zero Speed
to par. 1-53
V motors, set the nameplate data for 230 V/50 Hz. Adapt par. 4-13
[RPM]
Maximum Reference
and par. 3-03
Function:
Enter the nominal motor current value from the motor nameplate data. This data is used for cal-
culating motor torque, motor thermal protection, etc.
Function:
Enter the nominal motor speed value from the motor nameplate data. This data is used for calcu-
lating automatic motor compensations.
®
MG.33.AG.22 - VLT
is a registered Danfoss trademark
VLT
®
AutomationDrive FC 300 Instruction
[0].
Model Shift Frequency
. For 87 Hz operation with 230/400
Motor Speed High Limit
to the 87 Hz application.
Manual
Motor