Engineering and remote access
7.6 Cyclic and acyclic data
Data
Channel1 Ilimit
[10 mA]
Channel1 Ithreshold
(0-100 %)
Fill byte [s]
Channel1 output
voltage [10 mV]
Channel1 output
current [10 mA]
Channel1 max output
current 10 mA]
Channel1 Operation
mode
Channel1 parallel
mode (0/255)
Channel1 operation
state
210
Description
Response threshold of the output current for output 1. When this is exceeded,
the output current is interpreted as having an overload condition and is shut
down with a time delay - or limited.
Prewarning threshold of the configured response threshold for the output cur-
rent in %. An alarm is initiated when the actual output current exceeds this
value. Operation is continued without any restrictions. Prewarning is deactivat-
ed by entering "0 %".
-
Output voltage at output 1.
Output current at output 1.
Maximum output current at output 1.
Operating mode output 1:
If the actual load current
of an output exceeds the
specified response
threshold value of the
output current, then the
output can be shut down
according to a current-
time characteristic ("elec-
tronic shutdown"), or the
load current can be lim-
ited to the response
threshold ("constant cur-
rent").
Actual parallel connection for output:
0 = parallel connection deactivated
255 = parallel connection activated
Operating state output 1
0 = ModeSelect
Electronic shutdown: The
output is shut down when
the response threshold
value is exceeded.
1 = ModeModular
Constant current: When
the response threshold
value is exceeded, the
load current is limited to
the response threshold
until this is fallen below
again.
0 = ManualOff
Output switched off man-
ually (button):
1 = RemoteOff
Output switched off
(PROFINET/IE):
2 = BufferOff
Output switched off
3 = OverLoadOff
Output switched off (over-
load):
4 = ReadyForRestart
Output ready for reset:
5 = ErrorOff
Output switched off (fault)
6 = Boot
Output switched off (pow-
ering up)
7 = Running
Output switched on (nor-
mal operation)
8 = OverLoad
Output in overload opera-
tion:
9 = Limit
Output current limited to
the response threshold:
Data type
Unsigned16
Unsigned8
Unsigned8
Unsigned16
Unsigned16
Unsigned16
Unsigned8
Unsigned8
Unsigned8