Parameters
System start characteristics
Prewarning threshold output
current
Prewarning threshold output
current in the MANUAL
mode
Dead time for system over-
load alarm
Dead time for power supply
failure alarm
● Prioritized buffering of output 1
When the power fails, output 1 of the basic device can be prioritized so that it is still
supplied.
Prioritizing output 1 means that the longest possible buffer time is ensured for this output.
If output 1 is prioritized, all of the remaining outputs are shut down at approximately half
of the nominally available buffer time for the remaining duration of the power failure.
LEDs "ON/OFF/RST" of the outputs that have been shut down are lit red.
Outputs 2 ... n, which are shut down when the power fails as output 1 has priority, are
automatically switched-on again when the line supply returns.
For the basic device, the typical buffer time is 15 ms, additional buffer modules extend
the buffer time.
● Parallel connection of output 1 and output 2 / output 3 and output 4
Two outputs of a basic device can be connected in parallel to supply a load branch with a
current that is higher than the continuous maximum current of an individual output of the
basic device. This increases the available current rating.
The switchover to parallel operation means that the outputs involved are synchronized
and controlled together.
● System start characteristics
In order to reduce the load on the overall SITOP PSU8600 power supply system as a
result of simultaneous switch-on current peaks of the loads at the various outputs, an on
delay between the outputs can be selected when switching on.
When the on delay is activated, the outputs are sequentially switched-on with a 25 ms or
100 ms delay time between the outputs, or load optimized.
When the variable on delay is activated, you can assign individual on delay times to the
individual outputs.
● Prewarning threshold output current
When changes are made, the prewarning threshold for the summed current allows you to
quickly check the utilization of the overall system. This is especially of interest when
PSU8600power supply systems
Manual, 04.2016, A5E35883207-7-76
Value range
No on delay
25 ms on delay
100 ms on delay
Load-optimized on delay
Variable on delay
0 - 100 %
0 - 100 %
0 - 60000 ms
0 - 1000 ms
Engineering and remote access
7.5 Web server
Default setting
No on delay
90 %
90 %
5000 ms
0 ms
185