Siemens SITOP PSU8600 Manual page 229

Psu8600power supply systems
Hide thumbs Also See for SITOP PSU8600:
Table of Contents

Advertisement

Basic device
6EP3436-8MB00-2CY0
Operating display 3-color LED for the
device operating status;
LED for manual/remote
mode;
4 LED for PROFINET
communication;
3-color LED per output
for the output operating
status;
LED for parallel opera-
tion of outputs 1 and
2 / 3 and 4
Signaling
Relay contact (change-
over contact, rating
60 V DC /0.3 A) for
"OK"
Response when
No overshoot of U
switching on/off
Starting delay,
1 s
max.
Voltage rise
500 ms
time / of the out-
put volt-
age / maximum
Switching-in of
All outputs are simultaneously switched-on after the device powers up, after a delay time of 25 ms,
the outputs
100 ms – or "load optimized" where the outputs are sequentially switched-on, can be selected via DIP
switch
Rated current
20 A
I
out rated
Current range
0 - 20 A
50 - 60 °C:
Remark
Derating 2.5 %/K
(no derating in conjunction with the expansion
module SITOP CNX8600 and total load of the
outputs at the basic device max. 240 W or 480 W
(see Image 9-7 Output power as a function of the
ambient temperature for SITOP PSU8600
6EP3436-8MB00-2CY0 (Page 233) and Image 9-
8 Output power as a function of the ambient tem-
perature for SITOP PSU8600 6EP3437-8MB00-
2CY0 (Page 233))
Output current
5 A
per output
PSU8600power supply systems
Manual, 04.2016, A5E35883207-7-76
Basic device
6EP3437-8MB00-2CY0
3-color LED for the
device operating status;
LED for manual/remote
mode;
4 LED for PROFINET
communication;
3-color LED per output
for the output operating
status;
LED for parallel opera-
tion of outputs 1 and
2 / 3 and 4
Relay contact (change-
over contact, rating
60 V DC /0.3 A) for
"OK"
(Soft-Start)
out
1 s
500 ms
40 A
0 - 40 A
50 - 60 °C:
Derating 2.5 %/K
10 A
Expansion module
6EP4436-8XB00-0CY0
3-color LED for the
module operating sta-
tus;
3-color LED per output
for the output operating
status
Via relay contact, basic
device
1 s
500 ms
20 A
2)
0 - 20 A
2)
-
5 A
2)
Technical data
9.2 Output data
Expansion module
6EP4437-8XB00-0CY0
3-color LED for the
module operating sta-
tus;
3-color LED per output
for the output operating
status
Via relay contact, basic
device
1 s
500 ms
40 A
2)
0 - 40 A
2)
-
10 A
2)