Description, device design, dimension drawing
2.6 Displays
Table 2- 8
LED "ON/OFF/RST"
Signaling
Off
Green
Flashing green (0.25/0.25)
Flashing green (1/1)
Red
Flashing red (0.25/0.25)
Flashing red (1/1)
Yellow
Table 2- 9
LED "PARALLEL"
Signaling
Off
Green
Flashing green (1/1)
32
⑥
Device is off or is powering up (booting)
•
Or parallel connection function is active (only output 2 and/or 4)
•
Or ERROR OFF shutdown
•
Or incorrect hardware configuration (REMOTE mode)
•
Or firmware being updated/completed
•
Normal operation, output current < response threshold value
Overload at the output: Output current 101...150 % of the response threshold
(operation permissible up to 149 % for 5 s, 150 % for 200 ms
For overload, the output current is limited
To the response threshold value for the duration of the overload (CONSTANT
•
CURRENT mode)
to the rated value for 60 s for system overload
•
Output automatically shut down due to
Overload exceeding the permissible time range (ELECTRONIC SHUTDOWN
•
mode)
Output 1 prioritized for buffer mode
•
Overtemperature of the output (in pairs)
•
After automatic shutdown due to overload or overtemperature, output is ready for
reset by pressing the button, reset signal or control command
Output shut down via control command (REMOTE mode)
Output manually shut down using the button at the device
⑦
Device is OFF or is powering up (booting)
•
Device is operational and the parallel connection function is not activated
•
Parallel connection function activated
Parallel connection function activated; wiring fault identified
PSU8600power supply systems
Manual, 04.2016, A5E35883207-7-76