Connecting To Yokogawa Plc (Stardom) - Mitsubishi Electric GOT2000 Series Connection Manual

Graphic operation terminal
Hide thumbs Also See for GOT2000 Series:
Table of Contents

Advertisement

5.6.2

Connecting to YOKOGAWA PLC (STARDOM)

System Configuration
YOKOGAWA
PLC
Connection cable
Communic
controller
ation Type
Cable model
Twisted pair cable
• 10BASE-T
Shielded twisted
pair cable (STP) or
unshielded twisted
*1
STARDOM
pair cable (UTP):
Ethernet
(NFCP100,
Category 3, 4, and
NFJT100)
5
• 100BASE-TX
Shielded twisted
pair cable (STP):
Category 5 and 5e
*1
When connecting STARDOM to MODBUS
For details, refer to the following manual.
*2
When connect a GOT to a PLC, connect to the PCL Ethernet port via a hub.
Use cables, connectors, and hubs that meet the IEEE802.3 10BASE-T/100BASE-TX standards.
*3
When connecting GT2000 to an equipment that meets the 10BASE (-T/2/5) standard, use the switching hub and operate in an
environment where 10Mbps and 100Mbps can be mixed.
*4
A length between a hub and a node.
The maximum distance differs depending on the Ethernet device to be used.
The following shows the number of the connectable nodes when a repeater hub is used.
• 10BASE-T: Max. 4 nodes for a cascade connection (500m)
• 100BASE-TX: Max. 2 nodes for a cascade connection (205m)
When switching hubs are used, the cascade connection between the switching hubs has no logical limit for the number of
cascades.
For the limit, contact the switching hub manufacturer.
*5
Use the straight cable.
PLC Side Setting
Make the communication settings as shown below. For details of the communication settings, refer to the following
manual.
Peripheral Software Manual for YOKOGAWA PLC
POINT
POINT
POINT
Connection between STARDOM and the PC for communication settings
For the communication settings of STARDOM, STARDOM and the PC for communication settings must be
connected to Ethernet using the Resource Configurator (peripheral software).
Hub
Connection cable
External
Max.
device
*5
*4
distance
*2
100m
Hub
®
YOKOGAWA PLC user's Manual
GOT
Connection cable
Connection cable
Max.
*5
Cable model
*4
distance
Twisted pair cable
• 10BASE-T
Shielded twisted
pair cable (STP) or
unshielded twisted
pair cable (UTP):
100m
Category 3, 4, and
5
• 100BASE-TX
Shielded twisted
pair cable (STP):
Category 5 and 5e
/TCP, Modbus Communication Portfolio License is required.
5. MODBUS(R)/TCP CONNECTION
5.6 Example of Connection
Communication driver
MODBUS/TCP
*3
GOT
Number of
connectable
GOT
Option device
equipment
Model
126 GOTs
- (Built into GOT)
for 1 PLC
5
5 - 13