Got Ethernet Settings - Mitsubishi Electric GOT2000 Series Connection Manual

Graphic operation terminal
Hide thumbs Also See for GOT2000 Series:
Table of Contents

Advertisement

Item
Set whether or not to perform
*3
a living confirmation.
Living Confirmation
(Default: No)
Set the sampling to perform a
Living Confirmation
living confirmation.
*4
Cycle
(Default: 20s)
*2
For the interrupt output, select [TCP/IP].
*3
Select [Yes] only when [Protocol] is [TCP/IP].
*4
The setting value can be changed when the [Living
Confirmation] is [Yes].
POINT
POINT
POINT
(1) Special Interrupt Code
The following shows the compatibility between the
special interrupt codes and the event types.
Special
Interrupt Code
(Hex)
*1
Base Screen
Output when the screens are switched according to the
change in the switching device values assigned to 1/2.
*1:
Base Screen or Overlap Window 1/2 switches
20H
independently without being interlocked.
(Example of output)
When all the switching device values assigned to
the Base Screen and Overlap Window1/2 are
changed, 3 special interrupt codes are output.
21H
Output when Numerical/ASCII Input is completed.
Output when Recipe data transfer (read-out, write-in) is
22H
completed.
Output when Bar code, RFID data has been imported
23H
into GOT
(1) Communication interface setting by the Utility
The communication interface setting can be
changed on the Utility's [Communication setting]
after writing [Communication Settings] of project
data.
For details on the Utility, refer to the following
manual.
GOT2000 Series User's Manual (Utility)
(2) Precedence in communication settings
When settings are made by GT Designer3 or the
Utility, the latest setting is effective.
3 - 70
3. MICROCOMPUTER CONNECTION (ETHERNET)
3.5 GOT Side Settings
Description
Range
Yes/No
10 to 100s
Event type
*1
and Overlap Window
3.5.3

GOT Ethernet settings

Item
Set the IP address of the GOT.
GOT IP Address
(Default: 192.168.0.18)
Set the subnet mask for the
sub network. (Only for
connection via router)
Subnet Mask
If the sub network is not used,
the default value is set.
(Default: 255.255.255.0)
Set the router address of the
default gateway where the
Default Gateway
GOT is connected. (Only for
connection via router)
(Default: 0.0.0.0)
Peripheral S/W
Set the GOT port No. for the S/
Communication Port
W communication.
(Default: 5015)
No.
Set the GOT port No. for the
transparent function.
Transparent Port No.
(Default: 5014)
Description
Range
0.0.0.0 to
255.255.255.
255
0.0.0.0 to
255.255.255.
255
0.0.0.0 to
255.255.255.
255
1024 to 5010.
5014 to
65534
(Except for
5011, 5012,
5013 and
49153)
1024 to 5010.
5014 to
65534
(Except for
5011, 5012,
5013 and
49153)