Details of data items in message format
POINT
POINT
POINT
Data code during communication
Communication of the format 3 is performed in ASCII code. (excluding interrupt output)
Communication of the format 4 is performed in Binary code.
(1) Control codes
Symbol
EOT
ENQ
NAK
ACK
LF
CL
CR
(2) Command
Specifies the contents to access from the host to GOT.
The command is converted to a 1-digit ASCII code (Hex) and transmitted.
For details of the commands that can be used, refer to the following.
(3) Station No.
Station No. is used to identify the GOT with which the host communicates. (Setting range: 0 to 31)
In the format 3, the address notated in decimal is converted to a 2-digit ASCII code (Hex) and transmitted from
the upper digit.
In the format 4, the address notated in decimal is converted to a 1-digit Binary code (binary) and transmitted.
The GOT processes only commands whose station No. matches the "Host Address (0 to 31)" set at
"Communication Detail Settings". (The message of command whose station No. does not match is ignored.)
For setting method of "Communication Detail Settings", refer to the following.
(4) Address
Specifies the head No. of the device data to be read/written.
In the format 3, the address notated in hexadecimal is converted to a 4-digit ASCII code (Hex) and transmitted
from the upper digit.
In the format 4, the address notated in hexadecimal is converted to a 2-digit Binary code (binary) and
transmitted from the upper digit.
For details of the device range that can be accessed, refer to the following.
(5) Bit pattern
Specifies the pattern of the bits to change.
In the format 3, the address notated in hexadecimal is converted to a 2-digit ASCII code (Hex) and transmitted
from the upper digit.
In the format 4, the address notated in hexadecimal is converted to a 1-digit Binary code (binary) and
transmitted.
3 - 32
3. MICROCOMPUTER CONNECTION (ETHERNET)
3.4 Message Formats
ASCII code
04
End of Transmission
H
05
Enquiry (start of enquiry)
H
15
Negative ACK (error response)
H
06
Acknowledge (write completion response)
H
0A
Line Feed
H
0C
Clear
H
0D
Carriage Return
H
3.4.2 List of commands
3.5.1 Setting communication interface (Communication settings)
3.3 Device Data Area
■ Message format (3) Multi-point write in bit units (3) command (w/out station No.), multi-point
write in bit units (D) command (w/ station No.)