2.6 GOT Side Settings

2.6.1
Setting communication
interface (Communication
settings)
Controller setting
Set the channel of the equipment to be connected to the
GOT.
2.
1.
Select [Common]
[Controller Setting] from the
menu.
2.
The Controller Setting window is displayed. Select the
channel to be used from the list menu.
3.
Set the following items.
• Manufacturer: Others
• Controller Type:Computer
• I/F: Interface to be used
• Driver:Computer
4.
The detailed setting is displayed after Manufacturer,
Controller Type, I/F, and Driver are set.
Make the settings according to the usage
environment.

2.6.2 Communication detail settings

Click the [OK] button when settings are completed.
POINT
POINT
POINT
The settings of connecting equipment can be set and
confirmed in [I/F Communication Setting]. For details,
refer to the following.
1.1.2 I/F communication setting
Make the settings according to the usage environment.
3.
4.
Transmission Speed
Data Bit
Click!
Stop Bit
Parity
Host Address
Format
Interrupt Data Byte
Special Interrupt
Code
Control Method
32bit Storage
2. MICROCOMPUTER CONNECTION (SERIAL)
2.6.2
Communication detail settings
Item
Description
Set this item when change the
transmission speed used for
communication with the
connected equipment.
(Default: 19200bps)
Set this item when change the
data length used for
communication with the
connected equipment.
(Default: 7bits)
Specify the stop bit length for
communications.
(Default: 1bit)
Specify whether or not to
perform a parity check, and
how it is performed during
communication.
(Default: Even)
Specify the host address
(station No. of the PLC to
which the GOT is connected)
in the network of the GOT.
(Default: 0)
Select the communication
format.
(Default: 1)
Specify the number of bytes of
interrupt data.
(Default: 1byte)
Set whether or not to output
the special interrupt code.
(Default: No)
Set this item when selecting
the XON/XOFF control for the
control method.
(Default: No)
Select the steps to store two
words (32-bit data).
(Default: LH Order)
2.6 GOT Side Settings
2
Range
4800bps,
9600bps,
19200bps,
38400bps,
57600bps,
115200bps
7bits/8bits
1bit/2bits
None
Even
Odd
0 to 31
1 to 15
1byte, 2byte,
4byte
Yes or No
XON/XOFF,
No
LH Order/
HL Order
2 - 73