Particulate contamination
Table 31. Gaseous contamination specifications
Gaseous contamination
Copper coupon corrosion rate
Silver coupon corrosion rate
NOTE: Maximum corrosive contaminant levels measured at ≤50% relative humidity.

Standard operating temperature

Table 32. Standard operating temperature specifications
Standard operating temperature
Temperature ranges (for altitude less than 950
metres or 3117 feet)
Standard operating temperature restrictions

Expanded operating temperature

Table 33. Expanded operating temperature specifications
Expanded operating temperature
Continuous operation
44
Specifications
Residual dust present in the air must have a
deliquescent point less than 60% relative
humidity.
NOTE: This condition applies to data center
and non-data center environments.
Specifications
<300 Å/month per Class G1 as defined by ANSI/
ISA71.04-1985.
<200 Å/month as defined by AHSRAE TC9.9.
Specifications
10°C to 35°C (50°F to 95°F) with no direct sunlight
on the equipment.
NOTE: Maximum of 145 W 22–core processor
is supported in systems with eight 2.5-inch
drives 2–PCI slot chassis, and 75 W single
wide active GPU.
Ambient temperature is restricted to 30°C for
systems with eight 2.5-inches drives or ten 2.5-
inch drives chassis, with no PCIe SSD and a
maximum of 160 W workstation processor.
Ambient temperature is restricted to 30°C for
systems with ten 2.5-inch drives chassis, PCIe
SSD and a maximum of 135 W processor.
Ambient temperature is restricted to 35°C for
systems with ten 2.5-inch drives chassis, PCIe
SSD and a maximum of 120 W processor.
Ambient temperature is restricted to 35°C for
systems with twenty-four 1.8-inch drives
chassis, PCIe SSD, and a maximum of 135 W
processor.
Specifications
5°C to 40°C at 5% to 85% RH with 29°C dew point.