Operating temperature de-rating specifications

Table 17. Operating temperature
Operating temperature de-rating
Up to 35°C (95°F)
35°C to 40°C (95°F to 104°F)
40°C to 45°C (104°F to 113°F)

Particulate and gaseous contamination specifications

Table 18. Particulate contamination specifications
Particulate contamination
Air filtration
NOTE:
This condition applies only to data center environments. Air filtration requirements do not apply to IT equipment
designed to be used outside a data center, in environments such as an office or factory floor.
NOTE:
Air entering the data center must have MERV11 or MERV13 filtration.
Conductive dust
NOTE:
This condition applies to data center and non-data center environments.
Corrosive dust
Residual dust present in the air must have a deliquescent point less than 60% relative humidity.
NOTE:
This condition applies to data center and non-data center environments.
Table 19. Gaseous contamination specifications
Gaseous contamination
Copper coupon corrosion rate
Silver coupon corrosion rate
NOTE:
Maximum corrosive contaminant levels measured at ≤50% relative humidity.

Standard operating temperature specifications

NOTE:
All components including the DIMMs, communication cards, M.2 SATA, and PERC cards can be supported with
sufficient thermal margin if the ambient temperature is equal to or below to the maximum continuous operating temperature
listed in these tables with the exception of the Mellanox DP LP card.
Specifications
Maximum temperature is reduced by 1°C/300 m (1°F/547 ft)
above 950 m (3,117 ft).
Maximum temperature is reduced by 1°C/175 m (1°F/319 ft)
above 950 m (3,117 ft).
Maximum temperature is reduced by 1°C/125 m (1°F/228
Specifications
Data center air filtration as defined by
ISO Class 8 per ISO 14644-1 with a 95%
upper confidence limit.
Air must be free of conductive dust, zinc
whiskers, or other conductive particles.
Air must be free of corrosive dust.
Specifications
<300 Å/month per Class G1 as defined by ANSI/
ISA71.04-1985.
<200 Å/month as defined by AHSRAE TC9.9.
Technical specifications