Power Supplied As A Function Of Input Voltage (Left And Permissible Ups Overloads As A Function Of Time (Right); Appendix; Electrical Specifications; System Input/Output Power Ratings - MGE UPS Systems EX-11RT Installation And User Manual

Mge installation and user manual ups ex 5/7/11rt
Hide thumbs Also See for EX-11RT:
Table of Contents

Advertisement

5.0

Electrical Specifications

Electrical and Mechanical specifications for the EX 5/7/11RT.
5.1

System Input/Output Power Ratings

Table 5-1: EX 5/7/11 RT Voltages and Frequency Characteristics.
Source
Normal AC Source
Bypass AC Source
Load Output
(*): depends on output voltage setting, can be modified by software.
(**): set to +/- 4% by default, (1, 2, 4, 8% are possible values), can be modified by software.
5.2

System Overload Characteristics

Figure 5-1: Power supplied as a function of input voltage (left), and permissible UPS overloads as a function of time (right).
Load Percentage
100%
70%
120V
86-86000-00 B00
Voltage
156 to 280 VAC
160 to 242 VAC*
200/208/220/230/240/250VAC
(120/208/240Vac
are possible with
transformer module)
160V
280V
Load Percentage
1.5
1.25
1.1
1.02
U
0.5s
30s
60s

Appendix

Appendix
Frequency
40 to 70 Hz
58 to 62 Hz**
50/60 Hz autoranging
(or frequency converter)
120s
t
5 — 1