EX 5/7/11RT Systems
4.3

Re-connecting the Power Module

This operation can be performed without interrupting the load.
Figure 4-2: Reconnect the Power Module.
OFF
4 — 4
15
17
LOAD LEVEL
4 kW/ 5 kVA
ON
23
1. Secure the Input/Output box using the three
screws.
2. Reconnect the cables
Power Module.
3. Switch the battery circuit breaker(s)
the ON position.
4. Check if Normal AC source circuit breaker
8
is on the ON position.
5. Check that the LED
6. Turn the manual bypass switch from the
BYPASS to the NORMAL position.
7. Follow initial start up sequence (see section
3.1) in order to personalize the UPS.
8. Push the ON button
seconds.
The green LED
equipment is now protected by the UPS.