Table 3-1: Local Settings.
Display
Language
Date/time format
Date/time change
Audible alarm
Table 3-2: Output Features.
Display
Output voltage
Frequency converter
Output frequency
ECO mode
Hot standby
Operating mode
Bypass
Transfer
Interrupt time
Overload level
(*) : - Select "IT Network" for computer loads. Select "Industrial" for other applications or when there exists and absolute need
for service continuity (with potential 10msec. interrupt) when Bypass AC source is not within set tolerances.
See table 3-5 for more details
(**) UPS will switch to Bypass AC Source if it is within the set tolerances.
(***) Input voltage must be equal to output voltage.
Figure 3-3: Configuration used to provide cascade redundancy to critical loads.
Protective Device
Utility
AC Source
Protective Device
86-86000-00 B00
Factory setting
English
International
(DD-MM-YYYY/HH:MM)
Quick beeps
Factory setting
208 Volts AC (***)
Disabled
Auto ranging
Disabled
Disabled
Industrial
When bypass NOK
10 ms
102%
BYPASS AC
NORMAL AC
NORMAL AC
Options
French, Spanish, German, Italian
US
MM-DD-YYYY/HH:MM adjustable
Slow beeps
Options
200/208/220/230/240/250
Enabled
50/60 Hz
Enabled
Enabled
IT Network
When bypass OK (**)
10 to 200 ms
(by steps of 10 ms)
50/70%
Cascade redundancy configuration
offers better protection to critical
load, whereas the first UPS acts as
the Bypass AC Source for the
second UPS.
Operation
Installation and User Manual
Comments
Input voltage must be equal to
output voltage
Bypass AC source disabled
User selectable under
frequency converter mode
See section 3.4.2.
Full redundancy (see Figure 3-3)
(*) See Table 3-5.
(*) See Table 3-5.
Interrupt time calibration during
during load transfer when
Bypass AC source
is out of tolerances
LOAD
3 — 3

Hide quick links: