Battery Features; On/Off Features - MGE UPS Systems EX-11RT Installation And User Manual

Mge installation and user manual ups ex 5/7/11rt
Hide thumbs Also See for EX-11RT:
Table of Contents

Advertisement

EX 5/7/11RT Systems
Table 3-3: ON/OFF Features.
Display
Factory setting
Cold start
Disabled
Forced reboot
Enabled
Automatic restart
Enabled
Sleep mode
Disabled
Remote Command
Enabled
Table 3-4: Battery Features.
Display
Factory setting
Battery test
Every week
Pre-Alarm
20%
Runtime choice
UPS reads # and type
of Battery Modules
connected.
Battery deep discharge
Enabled
protection
3 — 4
Options
Enabled
Disabled
Disabled
Enabled
Disabled
Options
No test/daily/monthly
0 to 100%
From 50 to 400 Ah
Disabled
Operation
Comments
Start on battery.
UPS restarts automatically
when normal AC source
is restored.
UPS restarts automatically
when normal AC source
is restored.
Automatic shutdown on battery
if output load level <10%
Enables shutdown or restart
orders from software.
Comments
Low battery signal;1% increment
Requires CLA Module if using
options (see section 1.5.8)
If disabled, loss of
MGE UPS SYSTEMS, INC.
warranty.
86-86000-00 B00