Installation and wiring

5.4.1 Grounding

Risk of short circuits
70
If necessary, ground the instrument to increase the noise resistance.
For grounding purposes, use wiring with a minimum of 2mm
grounding connection should have a resistance of less than 100.
The point of grounding should be as close to the PLC as possible. The
ground wire should be as short as possible.
Always use an exclusive ground for PLCs and other devices. If two de-
vices share a single ground point, it may produce an adverse effect.
Q PLC
W Other device (inverter etc.)
Depending on the surroundings in which the equipment is used, grounding
may cause problems.
Example 1:
Since the power supply line of the FP0/FP0R expansion unit (24V DC and
0V terminal) is connected to the function earth through a varistor, the var-
istor may be shorted if there is an irregular potential between the power
supply line and function earth. (The power supply line of the FP0R is con-
nected to function earth through a high-voltage capacitor. Therefore, there
is no risk of a short-circuit.)
Power supply line of FP0R with built-in 39V varistor
Example 2:
Do not ground the function earth terminal of the FP0R when grounding a
plus terminal (+) of the power supply.
2
. The
FP0R User's Manual