Panasonic FP0R User Manual page 154

Programmable controllers
Hide thumbs Also See for FP0R:
Table of Contents

Advertisement

Communication
Operation mode flags
PLC link transmission error flag R9050
154
For PLC link 0: R9070 to R907F (correspond to station nos. 1 to 16)
For PLC link 1: R9090 to R909F (correspond to station nos. 1 to 16)
The operation modes (RUN/PROG) can be checked for any given PLC.
Flag
Station
System variable name
no.
no.
R9070
1
sys_bIsPlcLink0Station1InRunMode
R9071
2
sys_bIsPlcLink0Station2InRunMode
R9072
3
sys_bIsPlcLink0Station3InRunMode
R9073
4
sys_bIsPlcLink0Station4InRunMode
R9074
5
sys_bIsPlcLink0Station5InRunMode
R9075
6
sys_bIsPlcLink0Station6InRunMode
R9076
7
sys_bIsPlcLink0Station7InRunMode
R9077
8
sys_bIsPlcLink0Station8InRunMode
R9078
9
sys_bIsPlcLink0Station9InRunMode
R9079
10
sys_bIsPlcLink0Station10InRunMode
R907A
11
sys_bIsPlcLink0Station11InRunMode
R907B
12
sys_bIsPlcLink0Station12InRunMode
R907C
13
sys_bIsPlcLink0Station13InRunMode
R907D
14
sys_bIsPlcLink0Station14InRunMode
R907E
15
sys_bIsPlcLink0Station15InRunMode
R907F
16
sys_bIsPlcLink0Station16InRunMode
This flag turns to TRUE if a problem is detected during transmission.
Flag
Station
System variable name
no.
no.
R9050 1–16
sys_bIsPlcLink0-
TransmissionError
Conditions for
TRUE/FALSE
TRUE:
if the unit is in RUN
mode
FALSE:
if the unit is in PROG
mode
Conditions for TRUE/FALSE
TRUE:
if a transmission error has oc-
curred in the PLC link, or
if an error has occurred in the
setting of the PLC link area
FALSE:
if there are no transmission errors
FP0R User's Manual