N o t e
Station number setting for a PLC link
N o t e
FP0R User's Manual
PLC Link is only available via the COM port.
For RS232C connections, the maximum number of stations is 2.
For PLC Link, the communication format and baud rate settings
are fixed:
Data length: 8 bits
Parity:
Odd
Stop bit:
1 bit
Start code:
No STX
End code:
CR, use SendCharactersAndClearString for end code suppression
Baud rate
115200bit/s
The station number can be set within a range of 1 to 16. For details on set-
ting station numbers, see p. 102.
A maximum of 16 stations can be connected in a PLC link
# Station number of PLC
Make sure the same station number is not used for more than
one of the PLCs connected through the PLC Link function.
If there are fewer than 16 stations linked, set the highest station
number to reduce the link transmission cycle time. Station num-
bers should be set sequentially and consecutively, starting from
1, with no breaks between them. See "Setting the highest sta-
tion number for a PLC link" on p. 151.