Setting Communication Parameters - Panasonic FP0R User Manual

Programmable controllers
Hide thumbs Also See for FP0R:
Table of Contents

Advertisement

Communication
Modbus references and FP0R addresses
R e f e r e n c e

6.8.1 Setting communication parameters

N o t e
164
Modbus reference
Name
Coil
Input
Holding register C10, C14, C16
C32, T32, F32
Input register
1)
Beginning with 0
2)
Beginning with 1
For details on Modbus settings and communication, please refer to the
F145_WRITE_DATA and F146_READ_DATA commands in the FPWIN Pro
online help.
Make the following settings for the communication port:
communication mode (Modbus RTU)
station number
baud rate
communication format
For details on setting the communication parameters, see "Setting system
registers in PROG mode" on p. 102.
The station number can be set within a range of 1 to 99.
With a C-NET adapter, a maximum of 32 stations can be speci-
fied.
Decimal
Hexadecimal
address
address
1)
000001–001760
0000–06DF
002049–006144
0800–17FF
100001–001760
0000–06DF
400001–412315
0000–301B
40001–432765
0000–7FFC
300001–300128
0000–007F
302001–302256
07D0–08CF
PLC address
2)
Y0–Y109F
R0–R255F
X0–X109F
DT0–DT12314
DT0–DT32764
WL0–WL127
LD0–LD255
FP0R User's Manual